Understanding Voltage Drop
Voltage drop is the loss of voltage along a conductor caused by the wire's resistance. It matters because undersized wire wastes energy as heat, dims lights, makes motors run hot, and can cause code-compliant circuits to fail in real-world use. The National Electrical Code recommends keeping voltage drop under 3% for branch circuits and 5% combined with feeders.
Single-Phase Voltage Drop
Voltage drop increases with current and one-way distance, and decreases with larger conductors. The standard formula uses circular mils (CM) for wire area:
K is the material resistivity constant: 12.9 for copper, 21.2 for aluminum. L is one-way distance in feet. I is current in amps. The factor of 2 accounts for the hot and neutral conductors.
Three-Phase Voltage Drop
AWG to Circular Mils
| AWG | Circular Mils | mm2 | Typical Use |
|---|---|---|---|
| 14 | 4,107 | 2.08 | 15 A lighting |
| 12 | 6,530 | 3.31 | 20 A outlets |
| 10 | 10,380 | 5.26 | 30 A dryer |
| 8 | 16,510 | 8.37 | 40 A range |
| 6 | 26,240 | 13.3 | 50-60 A sub-panel |
| 4 | 41,740 | 21.2 | 85 A feeders |
| 2 | 66,360 | 33.6 | 100 A service |
| 4/0 | 211,600 | 107 | 200 A service |
NEC Recommended Drop Limits
- 3% maximum on branch circuits (outlets, lights, appliances) per NEC 210.19(A) Informational Note 4.
- 2% maximum on feeders when branch drop is at 3%, for a combined limit of 5% (NEC 215.2(A)(1) Informational Note 2).
- 5% maximum total from service entry to the farthest outlet, to ensure sensitive electronics and motors receive rated voltage.